Low Concrete Cylinder Strength -- What, why, & how?
|
|
|
WHAT Constitutes Low Cylinder Strength?
Strength test results of concrete cylinders are used as the basis of
acceptance of ready mixed concrete when a strength requirement
is specified. Cylinders are molded from a sample of fresh
concrete, cured in standard conditions and tested at a particular
age, as indicated in the specification, usually at 28 days. Procedures
must be in accordance with ASTM standards. The average
strength of a set of 2 or 3 cylinders made from the same concrete
sample and tested at 28 days constitutes one test. In some cases
cylinders are tested at 7 days to get an early indication of the
potential strength, but these test results are not to be used for
concrete acceptance. Cylinders used for acceptance of concrete
should not be confused with field-cured cylinders, which are
made to check early-age strength in the structure to strip forms
and continue construction activity.
The ACI Building Code, ACI 318, and the Standard Specifications
for Structural Concrete, ACI 301, recognize that when mixtures
are proportioned to meet the requirements of the standards,
low strength results will occur about once or twice in 100 tests
due to normal variability.
Under these provisions, for specified strength less than 5000 psi
(35 MPa), concrete is acceptable and complies with the specification
if:
- No single test is lower than the specified strength by more
than 500 psi (3.5 MPa), and
- The average of three consecutive tests equals or exceeds the
specified strength.
See the example in the table. If an average of three consecutive
tests in sequence falls below the specified strength, steps must
be taken to increase the strength of the concrete. If a single test
falls more than 500 psi (3.5 MPa) below the specified strength,
an investigation should be made to ensure structural adequacy
of that portion of the structure; and again, steps taken to increase
the strength level.
|

Effect of Non-Standard Curing on Compressive Strength

|
|
|
WHY are Compressive Tests Low?
Two major reasons are:
- Improper cylinder handling, curing and testing - found to
contribute in the majority of low strength results, and
- Reduced concrete strength due to an error in production, or
the addition of too much water to the concrete on the job due
to delays in placement or requests for wet concrete. High air
content can also be a cause of low strength.
In the event of low compressive strength test results, collect all
test reports and analyze the results before taking action. Look at
the pattern of strength results. Does the sequence actually violate
compliance with the specification as discussed above? Do
the test reports give any clue to the cause? The strength range of
two or three cylinders prepared from the same sample should
rarely exceed 8.0% or 9.5% of the average, respectively. Look at
the slump, air content, concrete and ambient temperatures, number
of days cylinders were left in the field, procedures used for
initial curing in the field and subsequent curing in the lab and any
reported cylinder defects.
If the deficiency justifies investigation, first verify testing accuracy
and then compare the structural requirements with the measured
strength. If testing is deficient or if strength is greater than
that actually needed in that portion of the structure, there is little
point in investigating the in-place strength. However, if procedures
conform to the standards and the strength as specified is
required for the structural capacity of the member in question,
further investigation of the in-place concrete may be required.
(See CIP- 10 on Strength of In-Place Concrete.)
Have testing procedures been conducted in accordance with the
ASTM standards? Minor deficiencies in curing cylinders in mild
weather will probably not affect strength much, but if major violations
are discovered, large reductions in strength can occur. Almost
all deficiencies in handling and testing cylinders will lower
strength. A number of violations may combine to cause significant
reductions in measured strength. Some of the more significant
factors are improperly finished surfaces, initial curing over
80°F (27°C); frozen cylinders; extra days in the field; impact
during transportation; delay in curing at the lab; improper caps;
and insufficient care in breaking cylinders.
The laboratory should be held responsible for deficiencies in its
procedures. Use of certified field-testing technicians and laboratory
personnel is essential; construction workers untrained in concrete
testing must not make and handle cylinders. All labs should
meet ASTM C 1077 criteria for laboratories testing concrete and
concrete aggregates and be inspected by the Cement and Concrete
Reference Laboratory (CCRL) laboratory inspection or an
equivalent program. Field testing personnel must have a current
ACI Grade I Field Testing Technician certification or equivalent.
Laboratory personnel should have the ACI Grade I and II Laboratory
Testing Technician and/or the ACI Strength Testing Certification,
or equivalent.
HOW to Make Standard Cylinder Tests?
All of the detailed steps from obtaining a sample, through molding,
curing, transporting, testing and reporting cylinder testing
are important. The following are critical procedures in the proper
application of the ASTM Standards for strength tests of fieldmade,
laboratory-cured cylinders:
- Sample concrete falling from chute in two increments, from
the middle part of the load, after some has been discharged.
- Transport sample to the location of curing for the first day.
- Remix the sample to ensure homogeneity.
- Use molds conforming to standards.
- Using a standard rod or vibrator, consolidate concrete in two
or three equal layers, as required, and tap sides of the mold to
close rod holes.
- Finish tops smooth and level to allow thin caps.
- If necessary, move cylinders immediately after molding; support
the bottom.
- For initial curing of cylinders at the jobsite during the first 24
to 48 hours, store cylinders in a moist environment maintained
at 60 to 80°F (16 to 27°C). If feasible, immerse the
molded cylinders in water maintained within this temperature
range. Curing boxes without temperature controls can
overheat and result in lower strengths.
- If the cylinders are stored exposed to the environment, keep
out of direct sunlight and protect from loss of moisture.
- Carefully transport one day-old cylinders to the laboratory;
handle gently.
- At the laboratory, demold the cylinders, transfer identifying
marking and promptly place in moist curing at 73±3°F
(23±2°C).
- Cure cylinders in the laboratory in accordance with ASTM C
31; maintain water on cylinder surfaces at all times.
- Determine the mass of the cylinder and record it. This information
is useful in troubleshooting low strength problems.
- Caps on cylinders must be flat and the average thickness less
than 1/4-inch (6-mm) and preferably less than 1/8-inch (3-
mm). This is especially significant when testing concrete with
strength exceeding 7000 psi (48 MPa).
- Use minimum 5000 psi (35 MPa) capping material. Restrict
the reuse of sulfur capping compound.
- Wait at least 2 hours and preferably longer for sulfur caps to
harden. Sulfur caps aged for 1 to 2 days often result in higher
strength, especially when testing concrete with strength exceeding
5000 psi (35 MPa).
- When using neoprene pad caps, ensure that the appropriate
Durometer hardness is used for the strength level tested; the
pad caps have been qualified for use; pads are not worn and
the permitted number of reuses have not been exceeded; see
ASTM C 1231. Worn pads will reduce the measured strength.
- Ensure that the testing machine is calibrated.
- Measure cylinder diameter and check cap planeness.
- Center cylinder on the testing machine and use proper loading
rate.
- Break the cylinder to complete failure. Observe failure pattern;
vertical cracks through the cap or a chip off the side
indicate improper load distribution.
Test reports must be promptly distributed to the concrete producer,
as well as the contractor and engineer. This is essential to
the timely resolution of problems.
|
|
|
References
- ASTM Standards C 31, C 39, C 172, C 470, C 617, C 1077, and C
1231, ASTM Book of Standards, Volume 04.02, American Society
for Testing and Materials, West Conshohocken, PA.
- Building Code Requirements for Reinforced Concrete, ACI 318,
American Concrete Institute, Farmington Hills, MI.
- Standard Specification for Structural Concrete, ACI 301, American
Concrete Institute, Farmington Hills, MI.
- In-Place Concrete Strength Evaluation-A Recommended Practice.
NRMCA Publication 133, NRMCA, Silver Spring, MD.
- Effect of Curing Condition on Compressive Strength of Concrete Test
Specimens, NRMCA Publication 53, NRMCA Silver Spring, MD.
- Review of Variables that Influence Measured Concrete Compressive
Strength, David N. Richardson, NRMCA Publication 179, NRMCA,
Silver Spring, MD.
- Low Strength Tests? Maybe Not! E.O. Goeb, Concrete Products, December
1992.
- Why Low Cylinder Tests in Hot Weather? E.O. Goeb, Concrete Construction,
Jan. 1986.
|
|
|