
 |
|
Testing the Compressive Strength of Concrete -- What, why, & how?
|
|
|
WHAT is Compressive Strength of Concrete?
Concrete mixtures can be designed to provide a wide range of mechanical
and durability properties to meet the design requirements
of a structure. The compressive strength of concrete is the most
common performance measure used by the engineer in designing
buildings and other structures. The compressive strength is measured
by breaking cylindrical concrete specimens in a compressiontesting
machine. The compressive strength is calculated from the
failure load divided by the cross-sectional area resisting the load
and reported in units of pound-force per square inch (psi) in US
Customary units or megapascals (MPa) in SI units. Concrete compressive
strength requirements can vary from 2500 psi (17 MPa)
for residential concrete to 4000 psi (28 MPa) and higher in commercial
structures. Higher strengths up to and exceeding 10,000
psi (70 MPa) are specified for certain applications.
|
 |
|
|
WHY is Compressive Strength Determined?
Compressive strength test results are primarily used to determine
that the concrete mixture as delivered meets the requirements of the
specified strength, ƒ′c, in the job specification.:
Strength test results from cast cylinders may be used for quality
control, acceptance of concrete, or for estimating the concrete strength
in a structure for the purpose of scheduling construction operations
such as form removal or for evaluating the adequacy of curing and
protection afforded to the structure. Cylinders tested for acceptance
and quality control are made and cured in accordance with procedures
described for standard-cured specimens in ASTM C 31 Standard
Practice for Making and Curing Concrete Test Specimens in the
Field. For estimating the in-place concrete strength, ASTM C 31
provides procedures for field-cured specimens. Cylindrical
specimens are tested in accordance with ASTM C 39, Standard Test
Method for Compressive Strength of Cylindrical Concrete
Specimens.
A test result is the average of at least two standard-cured strength
specimens made from the same concrete sample and tested at the
same age. In most cases strength requirements for concrete are at an
age of 28 days.
Design engineers us the specified strength ƒ´c to design structural
elements. This specified strength is incorporated in the job contract
documents. The concrete mixture is designed to produce an average
strength, ƒ′cr, higher than the specified strength such that the risk of
not complying with the strength specification is minimized. To
comply with the strength requirements of a job specification both
the following acceptance criteria apply:
- The average of 3 consecutive tests should equal or exceed the
specified strength, ƒ´c
- No single strength test should fall below ƒ´cby more than
500 psi (3.45 MPa); or by more than 0.10 ƒ´c when
ƒ´c is more than 5000 psi (35 MPa)
It is important to understand that an individual test falling
below ƒ´c does not necessarily constitute a failure to meet
specification requirements. When the average of strength tests
on a job are at the required average strength, ƒ′cr, the
probability that individual strength tests will be less than the
specified strength is about 10% and this is accounted for in
the acceptance criteria.
When strength test results indicate that the concrete delivered
fails to meet the requirements of the specification, it is
important to recognize that the failure may be in the testing,
not the concrete. This is especially true if the fabrication,
handling, curing and testing of the cylinders are not conducted
in accordance with standard procedures. See CIP 9, Low
Concrete Cylinder Strength.
Historical strength test records are used by the concrete
producer to establish the target average strength of concrete
mixtures for future work.
HOW to Test the Strength of Concrete
- Cylindrical specimens for acceptance testing should be 6 x 12
inch (150 x 300 mm) size or 4 x 8 inch (100 x 200 mm) when
specified. The smaller specimens tend to be easier to make and
handle in the field and the laboratory. The diameter of the
cylinder used should be at least 3 times the nominal maximum
size of the coarse aggregate used in the concrete.
- Recording the mass of the specimen before capping provides
useful information in case of disputes.
- To provide for a uniform load distribution when testing, cylinders
are capped generally with sulfur mortar (ASTM C 617) or
neoprene pad caps (ASTM C 1231). Sulfur caps should be
applied at least two hours and preferably one day before testing.
Neoprene pad caps can be used to measure concrete strengths
between 1500 and 7000 psi (10 to 50 MPa). For higher strengths
upto 12,000 psi, neoprene pad caps are permitted to be used if
they are qualified by companion testing with sulfur caps.
Durometer hardness requirements for neoprene pads vary from
50 to 70 depending on the strength level tested. Pads should be
replaced if there is excessive wear.
- Cylinders should not be allowed to dry out prior to testing.
- The cylinder diameter should be measured in two locations at
right angles to each other at mid-height of the specimen and
averaged to calculate the cross-sectional area. If the two
measured diameters differ by more than 2%, the cylinder should
not be tested.
- The ends of the specimens should not depart from perpendicularity
with the cylinder axis by more than 0.5º and the ends should be
plane to within 0.002 inches (0.05 mm).
- Cylinders should be centered in the compression-testing machine
and loaded to complete failure. The loading rate on a hydraulic
machine should be maintained in a range of 20 to 50 psi/s (0.15
to 0.35 MPa/s) during the latter half of the loading phase. The
type of break should be recorded. A common break pattern is a
conical fracture (see figure).
- The concrete strength is calculated by dividing the maximum
load at failure by the average cross-sectional area. C 39 has
correction factors if the length-to-diameter ratio of the cylinder
is between 1.75 and 1.00, which is rare. At least two cylinders
are tested at the same age and the average strength is reported
as the test result to the nearest 10 psi (0.1 MPa)
- The technician carrying out the test should record the date they
were received at the lab, the test date, specimen identification,
cylinder diameter, test age, maximum load applied, compressive
strength, type of fracture, and any defects in the cylinders or
caps. If measured, the mass of the cylinders should also be noted
- Most deviations from standard procedures for making, curing
and testing concrete test specimens will result in a lower
measured strength.
- The range between companion cylinders from the same set and
tested at the same age should be, on average, about 2 to 3% of
the average strength. If the difference between two companion
cylinders exceeds 8% too often, or 9.5% for three companion
cylinders, the testing procedures at the laboratory should be
evaluated and rectified.
- Results of tests made by different labs on the same concrete
sample should not differ by more than about 13% of the average
of the two test results.
- If one or both of a set of cylinders break at strength below ƒ´c,
evaluate the cylinders for obvious problems and hold the tested
cylinders for later examination. Frequently the cause of a failed
test can be readily seen in the cylinder, either immediately or by
petrographic examination. If it is thrown away an easy
opportunity to correct the problem may be lost. In some cases
additional reserve cylinders are made and can be tested if one
cylinder of a set broke at a lower strength.
- A 3 or 7-day test may help detect potential problems with
concrete quality or testing procedures at the lab but is not a
basis for rejecting concrete, with a requirement for 28-day or
other age strength.
- ASTM C 1077 requires that laboratory technicians involved in
testing concrete must be certified.
- Reports of compressive strength tests provide valuable information
to the project team for the current and future projects. The reports
should be forwarded to the concrete producer, contractor and
the owner’s representative as expeditiously as possible.
|
|
|
References
- ASTM C 31, C 39, C 617, C 1077, C 1231, Annual Book of ASTM
Standards, Volume 04.02, ASTM, West Conshohocken, PA,
www.astm.org
- Concrete in Practice Series, NRMCA, Silver Spring, MD,
www.nrmca.org
- In-Place Strength Evaluation - A Recommended Practice, NRMCA
Publication 133, NRMCA RES Committee, NRMCA, Silver Spring,
MD
- How producers can correct improper test-cylinder curing, Ward R.
Malisch, Concrete Producer Magazine, November 1997,
www.worldofconcrete.com
- NRMCA/ASCC Checklist for Concrete Pre-Construction Conference,
NRMCA, Silver Spring, MD
- NRMCA/ASCC Checklist for Concrete Pre-Construction Conference,
NRMCA, Silver Spring, MD
- Tips on Control Tests for Quality Concrete, PA015, Portland Cement
Association, Skokie, IL, www.cement.org
- ACI 214, Recommended Practice for Evaluation of Strength Tests
Results of Concrete, American Concrete Institute, Farmington Hills,
MI, www.concrete.org
|
|
|
Back to Tip Index |
|
|
USED WITH PERMISSION FROM THE NRMCA |
|
|